Carbon Dioxide Transmitter with Temp.&RH

Short Description:

Model: TGP Series
Key words:
CO2/Temperature/Humidity detection
External sensor probe
Analog linear outputs

 
It is mainly used in the application of BAS in industrial buildings to real time monitoring carbon dioxide level, temperature and relative humidity. Also suitable for applications in plant areas such as mushroom houses. The lower right hole of the shell can provide expandable use. The external sensor probe to avoid internal heating of the transmitter from affecting measurements. White backlight LCD can display CO2, Temp and RH if required. It can provide one, two or three 0-10V / 4-20mA linear outputs and a Modbus RS485 interface.


Brief Introduction

Product Tags

FEATURES

Real-time detect CO2 level of indoor environment
NDIR infrared CO2 sensor with Self-Calibration and up to 15 years lifetime
Humidity and temperature detection optional
Combined temperature and humidity sensor provide the highest accuracy in full range
Wall mounting with the external sensor probe with the higher accuracy of measurements
Backlit LCD display option can display CO2 measurement and temperature+ RH measurements
Providing one or three 0~10VDC or 4~20mA or 0~5VDC analog outputs
Modbus RS485 communication interface makes usage and test more convenient
Smart structure with the simple installation and wiring
CE-Approval

TECHNICAL SPECIFICATIONS

CO2 Sensor Non-Dispersive Infrared Detector (NDIR)
Measurement Range 0~2000ppm (default)

0~5000ppm selectable

Accuracy ±60ppm + 3% of reading @22℃(72℉)
Stability <2% of full scale over the life of the sensor
Calibration Self-calibration system
Response Time <5 minutes for 90% step change at low duct speed
Non-linearity <1% of full scale @22℃(72℉)
Pressure Dependence 0.135% of reading per mm Hg
Temperature Dependence 0.2% of full scale per ºC
Temperature & Humidity Sensor Temperature Relative Humidity

 

Sensing element: Band-gap-sensor Capacitive humidity sensor
Measuring range 0℃~50℃(32℉~122℉) (default) 0 ~100%RH
Accuracy ±0.5℃ (0℃~50℃) ±3%RH (20%-80%RH)
Display resolution 0.1℃ 0.1%RH
Stability ±0.1℃per year ±1%RH per year
General Data  
Power supply 24VAC/24VDC ±5%
Consumption 1.8 W max. ; 1.0 W avg.
 

LCD display

White backlit LCD display CO2 measurement

or CO2 + temperature& humidity measurements

 

Analog output

1 or 3 X analog outputs

0~10VDC(default) or 4~20mA (selectable by jumpers)

0~5VDC (selected at place the order)

Modbus RS485 Interface 19200bps, 15KV antistatic protection.
Operation conditions 0℃~50℃(32~122℉); 0~99%RH, non condensing
Storage conditions 0~60℃(32~140℉)/ 5~95%RH
Net weight 300g
IP class IP50
Standard Approval CE-Approval