In duct air quality sensor transmitter with CO2 and TVOC

Short Description:

Real time carbon dioxide and air quality (VOC) detection in air duct

High accuracy temperature and relative humidity

Smart sensor probe with extendable probe may be easily installed into any air duct

Equiped With the water-proof and porous film around the sensor probe

Up to 3 analog linear outputs for 3 measurements

Modbus RS485 interface for 4 measurements

With or without LCD display

CE-approval


Brief Introduction

Product Tags

FEATURES

Designed for real time detecting carbon dioxide, temperature or relative humidity in air ducts.
NDIR infrared CO2 sensor inside with special Self Calibration and up to 15 years’ lifetime. It makes CO2 measurement more accurate and reliable.
Combined temperature and humidity digital sensor provide a high accuracy measurement in full range.
Provide up to 3 analog outputs (0~10VDC or 4~20mA or 0~5VDC) for CO2 temperature and relative humidity.
Optional Modbus RS485 communication interface.
The end user can adjust CO2/Temp. range which correspond with the analog outputs Via Modbus, also can preset the direct proportion or inverse proportion for different applications.
With LCD or without LCD selectable
LCD display real-time measurements of CO2, temperature and relative humidity.
Simple and smart design and installation of sensor probe with a water-proof and porous film
Extendable probe meets more air duct systems
24VAC/VDC power supply.
EU standard and CE-approval.

TECHNICAL SPECIFICATIONS

Monitoring parameters

CO2

Temperature

Relative humidity
Sensing element Non-Dispersive Infrared Detector (NDIR) Digital combined temperature and humidity sensor
Measuring range

0~2000ppm(default) 0~5000ppm

(selectable in the order)

0℃~50℃(32℉~122℉) (default) 0~100%RH
Display Resolution

1ppm

0.1℃

0.1%RH
Accuracy@25(77) ±60ppm + 3% of reading

±0.5℃ (0℃~50℃)

±3%RH (20%-80%RH)

Life time

15 years (normal)

10 years

Calibration cycle ABC Logic Self Calibration

——

——

Response Time <2 minutes for 90% change <10 seconds to reach 63%
Warm up time 2 hours (first time)2 minutes (operation)

Electrical Characteristics

Power supply 24VAC/VDC
Consumption 3.5 W max. ; 2.5 W avg.

Outputs

Two or three analog outputs0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at place the order)
Modbus RS485 interface (optional) RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address

Conditions of Using and Installation

Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions 0~50℃(32~122℉)/ 5~80%RH

Weight

320g
Installation Fixed on the air duct with 100mm installation hole size
 IP class of the housing IP50 for no LCD IP40 for with LCD
Standard CE-Approval