Ozone Split Type Controller
FEATURES
- Real time monitoring air ozone concentration
- Electrochemical ozone sensor with temperature detection and compensation,
- humidity detection optional
- Split installation for display controller and external sensor probe, the probe can be
- externded into Duct / Cabin or placed in any other location.
- Ozone sensor probe is with a built-in fan to ensure smooth airflow
- Ozone sensor probe replaceable
- 1xON/OFF relay output to control ozone generator and ventilator
- 1x0-10V or 4-20mA analog linear output for ozone concentration
- Modbus RS485 communication
- Buzzer alarm available or disable
- 24VDC or 100-240VAC power supply
- Sensor failure indicator light
TECHNICAL SPECIFICATIONS
General Data | |
Power Supply | 24VAC/VDC±20% or 100~240VACselectable in purchasing |
Power Consumption | 2.0W (average power consumption) |
Wiring Standard | Wire section area <1.5mm2 |
Working Condition | -20~50℃/ 0~95%RH |
Storage Conditions | 0℃~35℃,0~90%RH (no condensation) |
Dimensions/ Net Weight |
Controller: 85(W)X100(L)X50(H)mm / 230gProbe: 151.5mm ∮40mm |
Connect cable length | 2 meter cable length between controller and sensor probe |
Qualify standard | ISO 9001 |
Housing and IP class | PC/ABS fireproof plastic material,Controller IP class: IP40 for G controller, IP54 for A controllerSensor probe IP class: IP54 |
Sensor Data | |
Sensing Element | Electrochemical Ozone sensor |
Sensor lifetime | >3 years, Sensor proble replaceable |
Warm up Time | <60 seconds |
Response Time | <120s @T90 |
Signal Update | 1s |
Measuring Range | 0-1000ppb(default)/5000ppb/10000ppb optional |
Accuracy | ±20ppb + 5% reading or ±100ppb (whichever is greater) |
Display Resolution | 1ppb (0.01mg/m3) |
Stability | ±0.5% |
Zero Drift | <2%/year |
Humidity Detection (option) | 1~99%RH |
Outputs | |
Analog Output | One 0-10VDC or 4-20mA linear output for ozone detection |
Analog Output Resolution | 16Bit |
Relay dry contact Output | One relay output to control ozone concentrationMax switching current 5A (250VAC/30VDC),resistance Load |
RS485 communication Interface | Modbus RTU protocol with 9600bps(default) 15KV antistatic protection |
Buzzer alarm | Preset alarm valueEnable / Disable preset alarm functionTurn off alarm manually through buttons |