Carbon Monoxide Monitor and Controller
Real-time monitoring air Carbon Monoxide concentration with optional temperature and humidity detection.
Display real-time CO measurement values and 1-hour average
1x 0-10V or 4-20mA analog linear output for CO measured value
2 on/off relay outputs for CO and temperature control
Modbus RTU or BACnet -MS/TP communication optional
Buzzer alarm for setpoint of carbon monoxide
Zero calibration operation
Provides powerful setting functions for different control requirements
24VAC/VDC power supply
FEATURES
TECHNICAL SPECIFICATIONS
General Data
Power Supply | 24VAC/VDC±20% |
Power Consumption | 3.2W |
Connection Standard | Wire cross-sectional area<1.5mm2 |
Operating Environment | -20-60℃, 0~95%RH |
Storage Environment | 0-60℃/ 0~90%RH,non-condensing |
Dimension/Net Weight | 150mm(L)×90mm(W)×42mm(H) |
Manufacturing Standard | ISO 9001 |
Housings and IP class | PC/ABS fire-proof material; IP30 protection class |
Design Standard | CE-EMC Approval |
Sensor
CO Sensor | Figaro electrochemical sensor |
Sensor Lifetime | More than 5 years Replaceable sensor module |
Warm Up Time | 60 minutes(first use) 2 minute(daily use) |
Response Time | <120 seconds |
Signal Refreshing | One second |
CO Range (Optional) | 0-100ppm(Default)/0-200ppm/0-300ppm/0-500ppm |
Accuracy | <1ppm±3% |
Stability | ±5% (over 900 days) |
Temperature Sensor(Optional | Capacitive sensor |
Measuring Range | -20℃-60℃ |
Accuracy | ±0.5℃ (10~40℃) |
Display Resolution | 0.1℃ |
Stability | ±0.1℃/year |
Outputs
LCD Display(Optional) | Display real-time measured values of carbon monoxide and temp. Humidity if optional |
Analog Output | 1x0-10VDC/4-20mA linear output for CO measured value |
Analog Output Resolution | 16Bit |
Relay Dry Contact outputs | One or two on/off relay outputs, max current 5A (230VAC/30VDC), Resistive load separately controls CO and Temperature |
RS485 Communication (Optional) |
Modbus RTU,communication baud:9600bps(Default)
BACnet MS/TP optional, communication baud:9600bps(Default) 15KV anti-static protection |
Red Backlight Alarm | LCD will be red after CO concentration exceeds the alarm setpoint |
Buzzer Alarm | Buzzer alarm once CO concentration exceeds the alarm setpoint The alarm can be temporarily turned off manually |