Duct CO2 Transmitter with Temp.&RH
FEATURES
Real time carbon dioxide detection in air duct
High accuracy temperature and relative humidity
with extendable air probe into air duct
Equiped With the water-proof and porous film around the sensor probe
Up to 3 analog linear outputs for 3 measurements
Modbus RS485 interface for 4 measurements
With or without LCD display
CE-approval
TECHNICAL SPECIFICATIONS
Monitoring parameters |
CO2 |
Temperature |
Relative humidity |
Sensing element | Non-Dispersive Infrared Detector (NDIR) | Digital combined temperature and humidity sensor | |
Measuring range |
0~2000ppm(default) 0~5000ppm (selectable in the order) |
0℃~50℃(32℉~122℉) (default) | 0~100%RH |
Display Resolution |
1ppm |
0.1℃ |
0.1%RH |
Accuracy@25℃(77℉) | ±60ppm + 3% of reading |
±0.5℃ (0℃~50℃) |
±3%RH (20%-80%RH) |
Life time |
15 years (normal) |
10 years |
|
Calibration cycle | ABC Logic Self Calibration |
—— |
—— |
Response Time | <2 minutes for 90% change | <10 seconds to reach 63% | |
Warm up time | 2 hours (first time)2 minutes (operation) | ||
Electrical Characteristics |
|||
Power supply | 24VAC/VDC | ||
Consumption | 3.5 W max. ; 2.5 W avg. | ||
Outputs |
Two or three analog outputs0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at place the order) | ||
Modbus RS485 interface (optional) | RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address | ||
Conditions of Using and Installation |
|||
Operation conditions | 0~50℃(32~122℉); 0~95%RH, non condensing | ||
Storage conditions | 0~50℃(32~122℉)/ 5~80%RH | ||
Weight |
320g | ||
Installation | Fixed on the air duct with 100mm installation hole size | ||
IP class of the housing | IP50 for no LCD IP40 for with LCD | ||
Standard | CE-Approval |