Design for real time detection and monitoring carbon dioxide and temperature. Humidity detection is optional
Particular LCD display with three color backlit (Green/Yellow/Red)
CO measurement range: 0~500ppm/0~1000ppm
Electrochemical CO sensor with up to 5 years lift time
Two stages alarm preset
Two alarm ways: buzzer alarm and backlight colours changeover
Provide up to 2 relay dry contact outputs to control a fan and an alarm
Provide 1X analog linear output (0~10VDC/4~20mA selectable) for the measurement
Modbus RS–485 communication interface, 15 KV antistatic protection, individual IP address
Replace the CO sensor by the end user available
Provide two easy methods for calibration and setup alarm points by end users: infrared remote controller or a software via RS485
Humidity measurement and display optional
24VAC/VDC power supply, also 230VAC power supply with a power adaptor
For more applications with wall-mounted type and portable type
Great performance with higher quality and lower price
Sensors | |
Gas Sensor | Electrochemical carbon monoxide sensor |
Sensor lifetime | Up to 5 years, replaceable |
Warm up time | 1hour (first time) |
Response Time | Within 60 seconds |
Signal Update | 1s |
CO Measuring Range | 0~500ppm(default)/0~1000ppm selectable |
Accuracy | <1ppm (at 20±5℃/ 50±20%RH) |
Stability | ±5% (over 900 days) |
Temperature
Humidity Sensor |
NTC5K
HS capacitive sensor |
Temp./Humidity sensor accuracy | ±0.5℃ /±5%RH |
Measurement range | -10℃~60℃ (14℉~140℉)/0~100%RH |
Electrical | |
Power Supply | 24VAC/VDC or 230VAC with the power adaptor selectable |
Power Consumption | 2.8W |
Wiring connections | 9 terminal blocks (max.) |
Wiring Standard | Wire section area<1.5mm2 |
Outputs | |
Analog Output | 0~10VDC or 4~20mA linear output selectable |
Analog Output Resolution | 16Bit |
Relay dry contact Output | Up to two dry-contact outputs
Max, switching current 3A (230VAC/30VDC), resistance Load |
Modbus Interface | Modbus RS-485 with 19200bps(default), other rates selectable
in the order. 15KV antistatic protection |
Conditions | |
Working Condition | -10℃~60℃ (14℉~140℉)/ 0~ 99% RH |
Storage Conditions | -10℃~60℃ (14℉~140℉)/ 0~ 95% RH |
LCD Display | Green-normally,
Yellow – first stage alarm, Red- second stage alarm. CO alarm points can be preset. |
Others | |
Net Weight | 190g |
Dimensions | 130mm(H)×85mm(W)×36.5mm(D) |
Installation Standard | 65mm×65mm or 85mmx85mm or 2”×4” wire box |
Manufacturing Process | ISO 9001 Certified |
Housing and IP class | PC/ABS fireproof plastic material, protection class: IP30 |
Compliance | EMC Directive 89/336/EEC |