Indoor Air Quality Monitor for CO2 TVOC
FEATURES
Real time indoor air quality monitoring with CO2 plus TVOC and Temp.&RH
NDIR CO2 sensor with special Self-Calibration makes the CO2 measurement more accurate and more reliable.
More than 10 years lifetime of CO2 sensor
More than 5 years lifetime of Semi-conductor TVOC (mix gases) sensor
Digital temperature and humidity sensor with more than 10 years lifetime
Three-color (green/yellow/red) LCD backlight for optimal/moderate/poor ventilation levels
Buzzer alarm available
Optional 1xrelay output to control a fan
Easy operation by the touch button
Perfect performance in low cost for IAQ detection and monitoring
220VAC or 24VAC/VDC power supply selectable; power adaptor available;
Desktop and wall mounting available
Application in classrooms, offices, hotels and other public rooms
TECHNICAL SPECIFICATIONS
Monitoring parameters |
CO2 |
TVOC |
Temperature |
Relative humidity |
Sensor |
Non-Dispersive Infrared Detector (NDIR) | Semiconductor mix gases sensor | Digital combined temperature and humidity sensor | |
Measuring range |
0~5000ppm |
1~30ppm |
-20~60℃ |
0~100%RH |
Display Resolution |
1ppm |
5ppm |
0.1℃ |
0.1%RH |
Accuracy@25℃(77℉) |
±60ppm + 3% of reading |
±10% |
±0.5℃ |
±4.5%RH |
Life time |
15 years (normal) |
5~7 years |
10 years |
|
Stability |
<2% |
—— |
<0.04℃per year | <0.5%RHper year |
Calibration cycle |
ABC Logic Self Calibration |
—— |
—— |
—— |
Response Time |
<2 minutes for 90% change |
<1 minute(for 10ppm hydrogen, 30ppm ethanol)
<5 minute (for a cigarette) in 20m2 room |
<10 seconds to reach 63% |
|
Warm up time |
72 hours (first time) 1 hour (operation) | |||
Electrical Characteristics |
||||
Power supply |
100~240VAC18~24VAC/VDC with the power adaptor available | |||
Consumption |
3.5 W max. ; 2.5 W avg. | |||
Display and Alarm |
||||
LCD Display |
Green: CO2<1000ppm (optimal air quality) TVOC: ▬ or ▬ ▬ (low pollution)
Yellow: CO2>1000ppm (moderate air quality) TVOC: ▬ ▬ ▬ or ▬ ▬ ▬ ▬ (medium pollution)
Red: CO2>1400ppm (poor air quality) TVOC: ▬ ▬ ▬ ▬ ▬ or ▬ ▬ ▬ ▬ ▬ ▬ (heavy pollution)
Two modes selectable: both CO2 and TVOC over the above setpoints(default) Either CO2 or TVOC over the above setpoint |
|||
Conditions of Using and Installation |
||||
Operation conditions |
-10~50℃(14~122℉); 0~95%RH, non condensing | |||
Storage conditions |
0~50℃(32~122℉)/ 5~90%RH | |||
Weight |
200g | |||
Dimensions |
130mm(L)×85mm(W)×36.5mm(H) | |||
Installation |
Desktop or wall mount (65mm×65mm or 85mmX85mm or 2”×4” wire box) | |||
Housing IP class |
PC/ABS, protection class: IP30 |