CO2 Sensor in Temperature and Humidity option

Short Description:

Designed for real-time monitoring of environmental CO2 concentrations and temperature and humidity
Built in NDIR infrared CO2 sensor. Self checking function,
Make CO2 monitoring more accurate and reliable
The CO2 module exceeds the 10year life
High precision temperature and humidity monitoring, optional transmission
The use of digital temperature and humidity sensors, the perfect realization of temperature
Compensation function of humidity to CO2 measurement
Three color backlit LCD provides intuitive warning function
A wide variety of wall mounting dimensions are available for easy use
Provide Modbus RS485 communication interface options
24VAC/VDC power supply
EU standard, CE certification


  • :
  • Brief Introduction

    Product Tags

    FEATURES

    Design for real time measuring ambiance carbon dioxide level and temperature +RH%
    NDIR infrared CO2 sensor inside with special Self Calibration. It makes CO2 measurement more accurate and more reliable.
    More than 10 years lifetime of CO2 sensor
    High accuracy temperature and humidity measurement
    Combined both humidity and temperature sensors seamlessly with the digital auto compensation
    Provide up to three analog linear outputs for measurements
    LCD is optional to display CO2 and temperature &RH measurements
    Optional Modbus communication
    24VAC/VDC power supply
    EU standard and CE-approval

    TECHNICAL SPECIFICATIONS

    Carbon Dioxide
    Sensing element Non-Dispersive Infrared Detector (NDIR)
    CO2 measuring range 0~2000ppm/ 0~5,000ppm, 10000ppm and 50000ppm is optional
    CO2 Accuracy @22℃(72℉) ±40ppm + 3% of reading or ±75ppm (whichever is greater)
    Temperature dependence 0.2% FS per℃
    Stability <2% of FS over life of sensor (15 year typical)
    Pressure dependence 0.13% of reading per mm Hg
    Calibration ABC Logic Self Calibration Algorithm
    Response time <2 minutes for 90% step change typical
    Signal update Every 2 seconds
    Warm-up time 2 hours (first time) / 2 minutes (operation)
    Temperature

    Humidity

    Measuring range 0℃~50℃(32℉~122℉) (default) 0 ~100%RH
    Accuracy ±0.4℃ (20℃~40℃) ±3%RH (20%-80%RH)
    Display resolution 0.1℃ 0.1%RH
    Stability <0.04℃/year <0.5%RH/year
    General Data
    Power supply 24VAC/VDC
    Consumption 1.8 W max. ; 1.2 W avg.
     Analog outputs 1~3 X analog outputs0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at placing the order)
    Modbus communication (optional) RS-485 with Modbus protocol, 19200bps rate, 15KV antistaticprotection, independent base address.
    Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing
    Storage conditions 10~50℃(50~122℉), 20~60%RH non condensing
    Net Weight 240g
    Dimensions 130mm(H)×85mm(W)×36.5mm(D)
    Installation wall mounting with 65mm×65mm or 2”×4”wire box
    Housing and IP class PC/ABS fireproof plastic material, protection class: IP30
    Standard CE-Approval

  • Previous:
  • Next:

  • Write your message here and send it to us