CO2 Monitor with Wi-Fi RJ45 and Data Logger
FEATURES
- Wall embedded installation or Wall surface installation
- LCD display or No LCD display
- Automatic screen brightness adjustment
- 3-color LED lights indicating three CO2 range
- 18~36Vdc/20~28Vac power supply or 100~240Vac power supply
- Real time CO2 monitoring and 24 hours average CO2
- Optional PM2.5 simultaneous monitoring or TVOC monitoring
- RS485 interface or Optional WiFi interface
TECHNICAL SPECIFICATIONS
General Data
Detection Parameters(max.) | CO2, Temp.& RH (optional PM2.5 or TVOC) |
Output (Optional) | RS485 (Modbus RTU) WIFI @2.4 GHz 802.11b/g/n |
Operating Environment | Temp:0~60℃ Humidity︰0~99%RH |
Storage Conditions | 0℃~50℃, 0~70%RH |
Power Supply | 24VAC/VDC±20%,100~240VAC |
Overall Dimension | 91.00mm*111.00mm*51.00mm |
Power consumption | Average 1.9w (24V) 4.5w( 230V) |
Installation(embedded) | Standard 86/50 pipe box (installation hole distance 60mm) American standard pipe box (installation hole distance 84mm) |
PM2.5 Data
Sensor | Laser particle sensor, light scattering method |
Measuring Range | 0~500μg ∕m3 |
Output Resolution | 1μg∕ m3 |
Accuracy (PM2.5) | <15% |
CO2 Data
Sensor | Non-Dispersive Infrared Detector (NDIR) |
Measuring Range | 400~5,000ppm |
Output Resolution | 1ppm |
Accuracy | ±50ppm + 3% of reading or 75ppm |
Temperature and Humidity Data
Sensor | High precision digital integrated temperature and humidity sensor |
Measuring Range | Temp: 0℃~60℃ Humidity:0~99%RH |
Output Resolution | Temp:0.01℃ Humidity:0.01%RH |
Accuracy | Temp:±0.8℃ Humidity:±4.5%RH |
TVOC Data
Sensor | Metal oxide gas sensor |
Measuring Range | 0.001~4.0mg/m |
Output Resolution | 0.001mg∕m3 |
Accuracy | <15% |
DIMENSIONS