Model: TG9-CO2+VOC
Key words:
CO2/TVOC/Temperature/Humidity detection
Duct installation
Analog linear outputs
Real time detect carbon dioxide plus tvoc (mix gases) of the air duct, also optional temperature and relative humidity. A smart sensor probe with the water-proof and porous film can be easily installed into any air duct. LCD display is available if required. It provides one, two or three 0-10V / 4-20mA linear outputs. The end user can adjust CO2 range which correspond with the analog outputs via Modbus RS485, also can preset the inverse proportion liner outputs for some different applications.


Brief Introduction

Product Tags

FEATURES

Real time carbon dioxide detection in air duct
High accuracy temperature and relative humidity
with extendable air probe into air duct
Equiped With the water-proof and porous film around the sensor probe
Up to 3 analog linear outputs for 3 measurements
Modbus RS485 interface for 4 measurements
With or without LCD display
CE-approval

 

TECHNICAL SPECIFICATIONS

Monitoring parameters

CO2

Temperature

Relative humidity
Sensing element Non-Dispersive Infrared Detector (NDIR) Digital combined temperature and humidity sensor
Measuring range

0~2000ppm(default) 0~5000ppm

(selectable in the order)

0℃~50℃(32℉~122℉) (default) 0~100%RH
Display Resolution

1ppm

0.1℃

0.1%RH
Accuracy@25(77) ±60ppm + 3% of reading

±0.5℃ (0℃~50℃)

±3%RH (20%-80%RH)

Life time

15 years (normal)

10 years

Calibration cycle ABC Logic Self Calibration

——

——

Response Time <2 minutes for 90% change <10 seconds to reach 63%
Warm up time 2 hours (first time)2 minutes (operation)

Electrical Characteristics

Power supply 24VAC/VDC
Consumption 3.5 W max. ; 2.5 W avg.

Outputs

Two or three analog outputs0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at place the order)
Modbus RS485 interface (optional) RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address

Conditions of Using and Installation

Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions 0~50℃(32~122℉)/ 5~80%RH

Weight

320g
Installation Fixed on the air duct with 100mm installation hole size
 IP class of the housing IP50 for no LCD IP40 for with LCD
Standard CE-Approval