Duct Air Quality CO2 TVOC Transmitter
FEATURES
Real time carbon dioxide detection in air duct
High accuracy temperature and relative humidity
with extendable air probe into air duct
Equiped With the water-proof and porous film around the sensor probe
Up to 3 analog linear outputs for 3 measurements
Modbus RS485 interface for 4 measurements
With or without LCD display
CE-approval
TECHNICAL SPECIFICATIONS
Monitoring parameters |
CO2 |
Temperature |
Relative humidity |
Sensing element | Non-Dispersive Infrared Detector (NDIR) | Digital combined temperature and humidity sensor | |
Measuring range |
0~2000ppm(default) 0~5000ppm (selectable in the order) |
0℃~50℃(32℉~122℉) (default) | 0~100%RH |
Display Resolution |
1ppm |
0.1℃ |
0.1%RH |
Accuracy@25℃(77℉) | ±60ppm + 3% of reading |
±0.5℃ (0℃~50℃) |
±3%RH (20%-80%RH) |
Life time |
15 years (normal) |
10 years |
|
Calibration cycle | ABC Logic Self Calibration |
—— |
—— |
Response Time | <2 minutes for 90% change | <10 seconds to reach 63% | |
Warm up time | 2 hours (first time)2 minutes (operation) | ||
Electrical Characteristics |
|||
Power supply | 24VAC/VDC | ||
Consumption | 3.5 W max. ; 2.5 W avg. | ||
Outputs |
Two or three analog outputs0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at place the order) | ||
Modbus RS485 interface (optional) | RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address | ||
Conditions of Using and Installation |
|||
Operation conditions | 0~50℃(32~122℉); 0~95%RH, non condensing | ||
Storage conditions | 0~50℃(32~122℉)/ 5~80%RH | ||
Weight |
320g | ||
Installation | Fixed on the air duct with 100mm installation hole size | ||
IP class of the housing | IP50 for no LCD IP40 for with LCD | ||
Standard | CE-Approval |